Diesel Generator
Standby Rating (KVA)
Maximum Prime Power Rating
Operating
Weight
(KG)
Diesel Tank Capacity
(Liters)
Prime Rating Diesel Consumption
(Liters / HR)
KVA
KW
Amps Per Phase
100%
75%
50%
18 kVA
16.5
13.2
23.8
610
45
4.4
3.4
2.6
22 kVA
20.0
16.0
28.9
615
5.3
3.9
2.9
33 kVA
30.0
24.0
43.3
1,095
230
7.0
5.2
3.8
44 kVA
40.0
32.0
57.7
1,245
245
9.4
7.1
5.1
55 kVA
50.0
72.2
11.8
8.9
6.4
65 kVA
60.0
48.0
86.6
1,315
13.6
10.2
88 kVA
80.0
64.0
115.5
1,435
18.2
9.5
NOTES:
* Power Calculations:
o We recommend you to base your maximum load at 75% of the prime power ratings.
o Most Generators output are designed at 27 degrees C and are subject to 7.5% de-rating at 50 degrees C and 10% at 55 degree C.
* Voltage, Frequency: Our Electricity Generators are tuned to Saudi voltage & frequency as follows:
o Voltage Line to Line = 400 Volts, Voltage Line to Neutral = 230 Volts
o Frequency = 50HZ, Power Factor = 0.8
o Generators may be converted to other voltage / frequency after prior arrangement.
* Trailers: Gensets may be rented with mobile trailers, to simplify delivery.
* Electrical Accessories: >> See separate section.